OPERATING PRINCIPLE The water softener ensures consistently good waterquality and removes hardness from the water. No chemicals, additives, or additional technical equipment are required – only standard regeneration salt is needed. The entire system is automatically cleaned during each regeneration. In the ion exchange process, water is passed over the ion exchange resin. Hardness formers such as calcium and magnesium ions are exchanged for sodium ions. When the capacity of the softening system is exhausted, the ion exchange resin is regenerated with brine, and the hardness-forming minerals are discharged into the wastewater. DIMENSIONS WEAK–60 WEAK–80 WEAK–100 WEAK–120 • A 730 730 730 730 • B 930 930 930 930 • C 965 965 965 965 • D 1080 1080 1080 1080 • E 1180 1180 1180 1180 • F 320 320 320 320 • G 520 520 520 520 All values (mm) TECHNICAL DATA WEAK–60 WEAK–80 WEAK–100 WEAK–120 • Resin quantity (litres) 15 20 25 30 • Capacity (m3 x dH) 60 80 100 120 • Salt per regeneration (kg)* 3 4 5 6 • Max. Salt supply (kg) 75 70 65 60 • Max. Flow rate (m3/h) 2.0 2.0 2.5 2.5 • Min./Max. Operating pressure (bar) 3/6 3/6 3/6 3/6 • Minimum/maximum water temperature (°C) 5/40 5/40 5/40 5/40 • Electrical connection (V/Hz) 230/50 230/50 230/50 230/50 • Length of power connection cable (m) 4.0 4.0 4.0 4.0 • Water connection (inch) 1 1 1 1 • Overflow angle connection (inch) 1/2 1/2 1/2 1/2 • Waste water connection (inch) 1/2 1/2 1/2 1/2 * for 200 g salt / litre resin Note: The water to be treated must be free of impurities, iron and manganese (less than 0.1 mg/l in each case). If connected to the public water supply, a system separator in accordance with DIN EN 1717 must be provided. A B C D E F G 65